Permit Number: C13-1360
Permit Type: Commercial Building Permit - None BldgCombo
Address: W 330 DIMOND BLVD Anchorage
Location:
Work Description:

3474 sq ft tire sales addition; parking revisions & minor landscaping changes / tb

**DO NOT ISSUE CO UNTIL PERMIT FOR ADA BATHROOM HAS BEEN SUBMITTED PER R. NOFFSINGER**

PERMIT FOR ADA BATHROOMS C14-1564 / TB

Status: Closed
Project Name: COSTCO
Review Type: Fire
Result: Correction
Result Date: 6/3/2013 3:26:39 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: C. Hill                                                                   Permit #: C13-1360

Phone: 267-4911                                                                       Date: 06/03/13

Email: hillcc#muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: COSTCO - 330 W. Dimond

 

 

Review Status:  6/3/13 Corrections required

 

GENERAL

This review is code compliance review based on the requirements of the International Building Code (IBC), 2009 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23.  This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.

 

Scope:  addition of 5003 s.f. tire sales area.

1.  Provide fire extinguishers as required per IFC 906, within the new addition.  Show size, tupe and location on plans.  This is an extra (high) hazard occupancy class per IFC table 906.2(1). 

2.  What is the heigth of the tire storage?  Verify ESFR sprinkler heads will be provided. 

3.  Alterations/additions to existing fire systems, to include the cooking hood, sprinkler, fire alarm system is required to be a separate submital, review and sub-permit.  Contact Mark Warren @ 907-267-4992 for any questions on this item and/or the assigned MOA Project Manger, Tony Barganier.