Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: 08 4165
Permit Type: Commercial Building Permit - None BldgAlter
Address: 8600 KING ST Anchorage
Location:
Work Description: Work Descr: Tenant improvement, Remarks: gjs/ Fees are due of $ 5119.80-gjs ask Gretchen if questions // ok to issue demo under this permit per M Panilo. -mgm 04/29/08 //
Status: Closed
Project Name: BABIES R US
Review Type: Fire System
Result: Approved
Result Date: 2/5/2009 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Provide horn strobe coverage in main entrance / Cart storage area. Area is open to the public. C(2): Provide horn strobe coverage in entrace to stoce room grid line 1A C(3): Provide horn strobe coverage in confenence/break rooms on grid lines 7B and 7C C(4): Provide horn strobe coverage on second level above grid lines 7A through 7C show this level on the plans C(5): re-submit 3 sets of draws with new battery calculations
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter