| Date | Status | Code | Description | Ref | Location | Comments |
| 9/22/2026 | | MechRgh | See comments | See Inspector Comments | Lone vented heater vent has been disconnected | Connect vent before running unit |
| 9/22/2026 | | MechRgh | See comments | See Inspector Comments | Heater vents on roof are ~5.5' from 3' parapet wall | Per 2018 IFGC 503.6.5 Vents 12" and under in size within 8' of a vertical wall need to be 1' higher than wall |
| 9/22/2026 | | MechRgh | See comments | See Inspector Comments | | Change order required for addition of gas regulators to serve existing UHs. |