Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 920882
Inspection Type: Mechanical Rough
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/22/2026 MechRghSee commentsSee Inspector CommentsLone vented heater vent has been disconnected Connect vent before running unit
9/22/2026 MechRghSee commentsSee Inspector CommentsHeater vents on roof are ~5.5' from 3' parapet wallPer 2018 IFGC 503.6.5 Vents 12" and under in size within 8' of a vertical wall need to be 1' higher than wall
9/22/2026 MechRghSee commentsSee Inspector Comments Change order required for addition of gas regulators to serve existing UHs.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter