Inspection #: 868253
Inspection Type: Final Plumbing
Inspector: N.Smith
Result: Correction
Comment: See corrections, all else okay. Email me stamped prints is fine.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/21/2025TransferPlumbFinalCommentsSee Inspector Comments1" air outlet horizontal to vertical Per provided plans sheet t1-1 'proposed vent rack view' there shall be a tee with a drain plug on the 1" air outlet horizontal to vertical transition. Plans sheet t1-2 'VST green machine compliance and installation notes' point 16. There shall be no pockets or liquid traps in any of the connected piping from the VST processor to the vent stack tie-in points.
8/21/2025TransferPlumbFinalCommentsSee Inspector CommentsPlansNo Muni stamped pans on site.