Inspection #: 829152
Inspection Type: Mechanical Rough
Inspector: N.Smith
Result: Correction
Comment: Gas test and installation of tees/valves/unions for gas regs approved. See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/22/2026TransferMechRghSee commentsSee Inspector CommentsLone vented heater vent has been disconnected Connect vent before running unit
9/22/2026TransferMechRghSee commentsSee Inspector CommentsHeater vents on roof are ~5.5' from 3' parapet wallPer 2018 IFGC 503.6.5 Vents 12" and under in size within 8' of a vertical wall need to be 1' higher than wall
9/22/2026TransferMechRghSee commentsSee Inspector Comments Change order required for addition of gas regulators to serve existing UHs.