| Date | Status | Code | Description | Ref | Location | Comments |
| 9/17/2026 | Corrected | MechRgh | See comments | See Inspector Comments | Gas regulators | Provide installation manual, vent limiters required for all indoor gas regulators per exception to IFGC 410.3. |
| 9/17/2026 | Corrected | MechRgh | See comments | See Inspector Comments | Gas regulators | As per 2018 IFGC 410.2 isolation valve & union required to serve each regulator. Valve shall be installed upstream of upstream tee, union shall be installed 1' from regulator. |
| 9/17/2026 | Transfer | MechRgh | See comments | See Inspector Comments | | Change order required for addition of gas regulators to serve existing UHs. |