Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 706868
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Approved
Comment: Electrical final approved. Upper and lower levels.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/25/2022CorrectedCorrect Below* Strap LFMC at disconnect within 12".  
3/25/2022CorrectedCorrect Below* Panel P13Update panel schedule.
3/25/2022CorrectedCorrect Below* Break counter area. Multiple circuits to single yoke or strap required handle tie to disconnect all ungrounded conductors simultaneously. See 210.7.
3/25/2022CorrectedCorrect Below* Indoor AC units. Flexible cord not permitted for replacement of chapter 3 wiring method approved for the area. Provide installation instructions for indoor unit.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS