| Date | Status | Code | Description | Ref | Location | Comments |
| 3/25/2022 | Corrected | Correct Below | * | | Strap LFMC at disconnect within 12". | |
| 3/25/2022 | Corrected | Correct Below | * | | Panel P13 | Update panel schedule. |
| 3/25/2022 | Corrected | Correct Below | * | | Break counter area. | Multiple circuits to single yoke or strap required handle tie to disconnect all ungrounded conductors simultaneously. See 210.7. |
| 3/25/2022 | Corrected | Correct Below | * | | Indoor AC units. | Flexible cord not permitted for replacement of chapter 3 wiring method approved for the area. Provide installation instructions for indoor unit. |