Inspection #: 702454
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Lower level area conditionally approved for use until 4/8/2022. See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/25/2022TransferCorrect Below* Strap LFMC at disconnect within 12".  
3/25/2022TransferCorrect Below* Panel P13Update panel schedule.
3/25/2022TransferCorrect Below* Break counter area. Multiple circuits to single yoke or strap required handle tie to disconnect all ungrounded conductors simultaneously. See 210.7.
3/25/2022TransferCorrect Below* Indoor AC units. Flexible cord not permitted for replacement of chapter 3 wiring method approved for the area. Provide installation instructions for indoor unit.