Inspection #: 701376
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/30/2022TransferCorrect Below* Panel.Update panel schedule with unique and specific circuit identification. Add east, west, main entry...etc.
3/30/2022TransferCorrect Below* Controllers-groundingProvide documentation for terminal if rated for multiple conductors, if not splice with approved means and terminate single conductor. Bonding jumper required to metal door ground stud.
3/30/2022TransferCorrect Below* Controllers. label for max overcurrent on controllers does not match overcurrent devices installed. Appear to be switched at install locations.
3/30/2022TransferCorrect Below* Controllers. Working clearances required per 110.26.