| Date | Status | Code | Description | Ref | Location | Comments |
| 3/30/2022 | Transfer | Correct Below | * | | Panel. | Update panel schedule with unique and specific circuit identification. Add east, west, main entry...etc. |
| 3/30/2022 | Transfer | Correct Below | * | | Controllers-grounding | Provide documentation for terminal if rated for multiple conductors, if not splice with approved means and terminate single conductor. Bonding jumper required to metal door ground stud. |
| 3/30/2022 | Transfer | Correct Below | * | | Controllers. | label for max overcurrent on controllers does not match overcurrent devices installed. Appear to be switched at install locations. |
| 3/30/2022 | Transfer | Correct Below | * | | Controllers. | Working clearances required per 110.26. |