Inspection #: 670094
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See Corrections Conditional Electrical Approved till 7/30/2021

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/8/2021TransferCorrect Below* Ice cream makersThis appliance unit needs to be equipped with attachment plug and shall be energized from a receptacle outlet. When using a cord type connection. 2017 NEC 400.10 (A) (B). Receptacles will need to be GFCI protected.
7/2/2021CorrectedCorrect Below* Roof top fanUnit calls for 15 amp MOP
7/2/2021CorrectedCorrect Below* Food Court above ceiling Transformer T-9 bonding jumper to the XO is undersized.
7/2/2021CorrectedCorrect Below* Food Court ceiling topT15, and T9 conduit entries into transformer need bushings.
7/2/2021CorrectedCorrect Below* Hot Dog cooker final connections incompleteHot Dog cooker receptacle will need to be GFCI protected circuits 50,52,54