Inspection #: 669863
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: Conditional electrical final approved till 7/9/2021 See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/2/2021TransferCorrect Below* Roof top fanUnit calls for 15 amp MOP
7/2/2021TransferCorrect Below* Food Court above ceiling Transformer T-9 bonding jumper to the XO is undersized.
7/2/2021TransferCorrect Below* Food Court ceiling topT15, and T9 conduit entries into transformer need bushings.
7/2/2021TransferCorrect Below* Hot Dog cooker final connections incompleteHot Dog cooker receptacle will need to be GFCI protected circuits 50,52,54
7/1/2021CorrectedCorrect Below* Upper mechanical areaIndustrial control panel for Ansil calls for 15 amp max OCP for control board. Label circuits and Panels that feed control panel.