Inspection #: 668849
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/1/2021TransferCorrect Below* Upper mechanical areaIndustrial control panel for Ansil calls for 15 amp max OCP for control board. Label circuits and Panels that feed control panel.
6/25/2021TransferCorrect Below* Taylor brand ice cream maker and beverage cooler- units 831 and 856Ratings on equipment shown as 20 amp and 15 amp max supply over current protection. Circuits 8, 10 need to be protected by a 15 amp GFCI breaker.
6/25/2021TransferCorrect Below* Hot dog cooker final connections incomplete. Hot dog cooker receptacle will need to be GFCI protected circuits 50, 52, 54
6/25/2021CorrectedCorrect Below* High 120 volt receptacle. Ready access for GFCI protection required.
6/17/2021TransferCorrect Below* Kitchen AreaAll receptacles that fit the category described in 2017 NEC 210.8 B shall be GFCI protected. Includes ceiling receptacles, water booster pump, water reverse osmosis system, circuits 44, 45.