Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 667246
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/25/2021TransferCorrect Below* Taylor brand ice cream maker and beverage cooler- units 831 and 856Ratings on equipment shown as 20 amp and 15 amp max supply over current protection. Ice cream maker has 30 amp rated plugs. Properly rated plug, receptacles, and overcurrent protection required to supply units.
6/25/2021TransferCorrect Below* Hot dog cooker final connections incomplete.  
6/25/2021TransferCorrect Below* High 120 volt receptacle. Ready access for GFCI protection required.
6/17/2021CorrectedCorrect Below* Kitchen AreaAnsil remains to be wired, and Hood install is incomplete.
6/17/2021CorrectedCorrect Below* KitchenAdded receptacle on outside wall of the cooler is incomplete.
6/17/2021TransferCorrect Below* Kitchen AreaAll receptacles that fit the category described in 2017 NEC 210.8 B shall be GFCI protected. Includes ceiling receptacles, water booster pump, water reverse osmosis system, circuits 55 57, and circuits 50 52 54 receptacles.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter