Inspection #: 666524
Inspection Type: Final Mechanical
Inspector: E.Wood
Result: Approved
Comment: All corrections addressed. Points of attachment per the differed submittals, Approved. Mechanical Approved for final.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/15/2021CorrectedMechFinal16Deferred SubmittalsDeferred submittals are required for rooftop equipment- AMC23.10.104.8.12RTUMOA approved deferred submittals required showing engineered form of attachment related to all equipment weighing over 400#s.
6/15/2021CorrectedMechFinalSee commentsSee Inspector CommentsRTUCondensate trap required.
6/15/2021CorrectedMechFinal12Hood and Makeup AirHood and mechanical make-up air systems  shall be automatically controlled to start and operate simultaneously with the exhaust system- IMC 508.1Grease hood/make up airFunctional interlock required.
6/15/2021CorrectedMechFinal14Type I Exhaust Fan Drain <p>Vertical&nbsp;upblast type I hood exhaust fan shall have an approved drain outlet and grease reservoir IMC 506.5.2</p> Grease duct exhaust fanGrease drain catch required.