Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 648501
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: Inspection of kitchen only not for above ceiling. Approved for moving kitchen equipment in only. See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/17/2021TransferCorrect Below* Kitchen AreaAnsil remains to be wired, and Hood install is incomplete.
6/17/2021TransferCorrect Below* KitchenAdded receptacle on outside wall of the cooler is incomplete.
6/17/2021TransferCorrect Below* Kitchen AreaAll receptacles that fit the category described in 2017 NEC 210.8 B shall be GFCI protected. Includes ceiling receptacles, water booster pump, water reverse osmosis system, circuits 55 57, and circuits 50 52 54 receptacles.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter