Inspection #: 602179
Inspection Type: Mechanical Inspection
Inspector: K.Hanson
Result: Correction
Comment: All else OK, see corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/20/2020CorrectedMechCommentsSee commentsSee comments belowCrawlspace gas pipingInsufficient support. Provide support at required intervals (every 8' for 3/4") per pg. 26 of install guide.
2/20/2020CorrectedFurnRplCommentsSee inspector commentsGas line serving wall furnaceGas test failed, witnessed at 1psi.