Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 566020
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Approved
Comment: Requested by: Curtis Bosak 9077484916 cb@sei-ak.com Electrical upgrades in meat and food prep areas. Electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/31/2019Corrected01See inspection comments Meat packing room.120V cord drop receptacle(s) within 6 feet of sink(s) require GFCI protection. (Cord drop 120V receptacles not within 6 feet of sinks do not require GFCI protection).
5/31/2019Corrected01See inspection comments Rooftop rotisserie chicken EFs and MAU.Label as to panel and circuits supplying units and description corresponding to panel schedule.
5/31/2019Corrected01See inspection comments Circuits supplying rooftop mounted rotisserie chicken exhaust fans.Labelled for 15A OCPD max.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS