| Date | Status | Code | Description | Ref | Location | Comments |
| 5/31/2019 | Transfer | 01 | See inspection comments | | Meat packing room. | 120V cord drop receptacle(s) within 6 feet of sink(s) require GFCI protection. (Cord drop 120V receptacles not within 6 feet of sinks do not require GFCI protection). |
| 5/31/2019 | Transfer | 01 | See inspection comments | | Rooftop rotisserie chicken EFs and MAU. | Label as to panel and circuits supplying units and description corresponding to panel schedule. |
| 5/31/2019 | Transfer | 01 | See inspection comments | | Circuits supplying rooftop mounted rotisserie chicken exhaust fans. | Labelled for 15A OCPD max. |