Inspection #: 553541
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: Exterior electrical wall rough approved. Corrections for service and for connectors used at exterior lighting and receptacles.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/7/2019Transfer01See inspection comments Post available fault current and date calculated.  
3/7/2019Transfer01See inspection comments GEC to water and gas bond incomplete.  
3/7/2019Transfer01See inspection comments Exhaust fan at bathroom incomplete.  
3/7/2019Transfer01See inspection comments Romex connectors used at exterior junction boxes. Replace with MC connectors.  