Click Here To View Another Inspection Inspection #: 536577 Inspection Type: Emergency Gen NFPA 110 load Test Inspector: B.Meinhardt Result: Correction Comment: 10/16/2018Generator Failed to meet the 100 percent load bank test of 2010 NFPA 110 section 7.13.4.3. Generator rating is 500KW, 480 volts, 60 hz, 1800 RPM. During testing the generator was only able to obtain the following results: 490KW, 433 volts, 56.2 hz, 1715 RPM. Building load test not performed, still needs to be completedBart Meinhardt - AFD Fire Inspector Inspection Corrections DateStatusCodeDescriptionRefLocationComments