Inspection #: 536576
Inspection Type: Emergency Generator Final
Inspector: B.Meinhardt
Result: Approved
Comment: Will be doing a NFPA 110 Test on the EM Generator starting @ 1PM and will have the Derating Letter from Generac prior to the test. Requested by: Rick Novotny (907)632-6603 rn@sei-ak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/31/2019 EmerGenFinalOtherEmergencyGeneratorFinalOtherPlease correct the following: Generator approved for CO.&nbsp;&nbsp;<div><br></div><div>Notes:</div><div>Generator is designed to produce 500kw on #2 diesel fuel.&nbsp; It is derated to 450KW on #1 diesel fuel.&nbsp; Testing was complete with #2 diesel to achieve factor rated name plate load, but will be changed to #1 diesel for winter time operation.</div>