| Date | Status | Code | Description | Ref | Location | Comments |
| 10/26/2017 | Transfer | Fire 13 | Correction(s) #1 | Please correct the following: | | (1) Need submit permit and drawing to install 5 fire alarm horn strobes or strobes in the following areas : outside room east side, outside room south side, Inside room drop ceiling, inside room entrance, in cooler. Need to install manual fire alarm pull stations to the 2 exit doors with in 5 feet. (2) Will need to inspect south exit doors after delayed egress hardware installed. (3) Exit signs and light are not operation - need to demonstrate the operation on emergency power. Will reciece run report for generator to accept or require full operational test. (4) Horizonal sliding doors to have placard placed that state to be unlocked will occupied (5) exit doors to main store one of the door panels must be 32 inches wide. 2012 IFC 1008.1.1 |
| 10/26/2017 | Transfer | Fire 13 | Correction(s) #1 | Please correct the following: | | |
| 10/26/2017 | Transfer | Fire 2 | CCO approval | Fire Final approved for CCO | | CCO approved. Expires 11/26/2013. |