Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 472109
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: Correction
Comment: Requested by: D.J. Jaure 4063817668 dj@tc-const.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/25/2017TransferFire 13Correction(s) #1Please correct the following: (1) Need submit permit and drawing to install 5 fire alarm horn strobes or strobes in the following areas : outside room east side, outside room south side, Inside room drop ceiling, inside room entrance, in cooler. Need to install manual fire alarm pull stations to the 2 exit doors with in 5 feet. (2) Fire sprinkler system install is not complete and need installers certification from GMW Fire Protection (3) New exit south doors are stick and will not open one side - no more than 5 pound of force to open the doors 2012 IFC 1008.1.3 (4) Exit signs and light are not operation - need to demonstrate the operation on emergency power. (5) Horizonal sliding door need exit verbiage for break away doors and horizontal sliding doors need battery back up 2012 IFC 1008.1.4.3 (6) exit doors to main store one of the door panels must be 32 inches wide. 2012 IFC 1008.1.1
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS