| Date | Status | Code | Description | Ref | Location | Comments |
| 8/21/2017 | Transfer | 01 | See inspection comments | | Above ovens, proof box. | Equipment needs disconnects within sight |
| 8/21/2017 | Transfer | 01 | See inspection comments | | 120V cord drop receptacles. | Need GFCI protection. |
| 8/21/2017 | Transfer | 01 | See inspection comments | | Boxes feeding cord drop receptacles. | At least (1) box does not have a spreader bar to fasten it to the grid. Others do not have seismic support wires. |
| 8/21/2017 | Transfer | 01 | See inspection comments | | Above bakery ceiling general. | Conduits not properly supported; support wires need to tie to the grid. Many flex conduits, MC run on ceiling tiles |
| 8/21/2017 | Transfer | 01 | See inspection comments | | Above bakery ceiling general | Open j-boxes. At least one open j-box contains feeder conductors that are not safed off.. Ground wire not bonded to the box. |
| 8/21/2017 | Transfer | 01 | See inspection comments | | Above bakery ceiling general. | Remove cords. |