Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 469578
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Electrical above existing bakery grid ceiling has many code compliance issues.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/21/2017Transfer01See inspection comments Above ovens, proof box.Equipment needs disconnects within sight
8/21/2017Transfer01See inspection comments 120V cord drop receptacles.Need GFCI protection.
8/21/2017Transfer01See inspection comments Boxes feeding cord drop receptacles.At least (1) box does not have a spreader bar to fasten it to the grid. Others do not have seismic support wires.
8/21/2017Transfer01See inspection comments Above bakery ceiling general.Conduits not properly supported; support wires need to tie to the grid. Many flex conduits, MC run on ceiling tiles
8/21/2017Transfer01See inspection comments Above bakery ceiling generalOpen j-boxes. At least one open j-box contains feeder conductors that are not safed off.. Ground wire not bonded to the box.
8/21/2017Transfer01See inspection comments Above bakery ceiling general.Remove cords.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter