Inspection #: 329841
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Please call Brandon @ 887-9132 209 minutes prior to inspection Requested by: brandon marshall 887-9132 brandon@marshallselectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/29/2014 EF1Correct Below GeneralMay be more.
10/29/2014 EF1Correct Below Comtrollers for air curtains: entry.Will need ladder to reinspect. Drawings show electrical contractror making all final connections.
10/29/2014 EF1Correct Below Any panels added as part of this remodel.Verify compliance with NEC 408.4(B): label to indicate source of supply.
10/29/2014 EF1Correct Below Any new transformers added as part of this remodel.Verify compliance with NEC 450.14: XFMRs other than class 2 or class 3 required to have a disconnect within sight or to have breaker lock if source of supply or disconnect is out of sight. Also, if source of supply is out of sight, XFMR required to be labelled as to source of supply.
10/27/2014 EF1Correct Below 277V-120V control transformer.Ground one leg. Use ground bar.
10/27/2014 EF1Correct Below Sales floor large fans 
10/27/2014 EF1Correct Below Sales floor large fans. 
10/27/2014 EF1Correct Below Change order dwgs.Confirm that OCPD size, panel conforms to dwgs.
10/27/2014 EF1Correct Below Sales floor large ceiling fansCannot have hardwired SO cord.
10/27/2014 EF1Correct Below Sales floor large ceiling fans.Disconnects within the fan blade radius or located so that fan blades violate working clearances.
10/27/2014 EF1Correct Below Entry heaters Tork digital time switches.Cannot use green wire as hot jumper.
10/27/2014 EF1Correct Below Sales floor.Several large ceiling paddle fans not shown on dwgs. Who did this work?
10/27/2014 EF1Correct Below Freezer condensate heat trace.Needs GFPE.
10/27/2014 EF1Correct Below Rooftop AC3WR recept. In use cover.
10/27/2014 EF1Correct Below Entry pnl feeding htrs, air curtains.Make breaker designations specific.
10/27/2014 EF1Correct Below Change orderComplete, show new pnl feeding entry ckts