| Date | Status | Code | Description | Ref | Location | Comments |
| 10/29/2014 | | EF1 | Correct Below | | General | May be more. |
| 10/29/2014 | | EF1 | Correct Below | | Comtrollers for air curtains: entry. | Will need ladder to reinspect. Drawings show electrical contractror making all final connections. |
| 10/29/2014 | | EF1 | Correct Below | | Any panels added as part of this remodel. | Verify compliance with NEC 408.4(B): label to indicate source of supply. |
| 10/29/2014 | | EF1 | Correct Below | | Any new transformers added as part of this remodel. | Verify compliance with NEC 450.14: XFMRs other than class 2 or class 3 required to have a disconnect within sight or to have breaker lock if source of supply or disconnect is out of sight. Also, if source of supply is out of sight, XFMR required to be labelled as to source of supply. |
| 10/27/2014 | | EF1 | Correct Below | | 277V-120V control transformer. | Ground one leg. Use ground bar. |
| 10/27/2014 | | EF1 | Correct Below | | Sales floor large fans | |
| 10/27/2014 | | EF1 | Correct Below | | Sales floor large fans. | |
| 10/27/2014 | | EF1 | Correct Below | | Change order dwgs. | Confirm that OCPD size, panel conforms to dwgs. |
| 10/27/2014 | | EF1 | Correct Below | | Sales floor large ceiling fans | Cannot have hardwired SO cord. |
| 10/27/2014 | | EF1 | Correct Below | | Sales floor large ceiling fans. | Disconnects within the fan blade radius or located so that fan blades violate working clearances. |
| 10/27/2014 | | EF1 | Correct Below | | Entry heaters Tork digital time switches. | Cannot use green wire as hot jumper. |
| 10/27/2014 | | EF1 | Correct Below | | Sales floor. | Several large ceiling paddle fans not shown on dwgs. Who did this work? |
| 10/27/2014 | | EF1 | Correct Below | | Freezer condensate heat trace. | Needs GFPE. |
| 10/27/2014 | | EF1 | Correct Below | | Rooftop AC3 | WR recept. In use cover. |
| 10/27/2014 | | EF1 | Correct Below | | Entry pnl feeding htrs, air curtains. | Make breaker designations specific. |
| 10/27/2014 | | EF1 | Correct Below | | Change order | Complete, show new pnl feeding entry ckts |