Inspection #: 329566
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/27/2014TransferEF1Correct Below 277V-120V control transformer.Ground one leg. Use ground bar.
10/27/2014TransferEF1Correct Below Comtrollers for air curtains: entry.Will need ladder to reinspect. Drawings show electrical contractror making all final connections.
10/27/2014TransferEF1Correct Below Sales floor large fans 
10/27/2014TransferEF1Correct Below Sales floor large fans. 
10/27/2014TransferEF1Correct Below Change order dwgs.Confirm that OCPD size, panel conforms to dwgs.
10/27/2014TransferEF1Correct Below GeneralMay be more.
10/27/2014TransferEF1Correct Below Any panels added as part of this remodel.Verify compliance with NEC 408.4(B): label to indicate source of supply.
10/27/2014TransferEF1Correct Below Any new transformers added as part of this remodel.Verify compliance with NEC 450.14: XFMRs other than class 2 or class 3 required to have a disconnect within sight or to have breaker lock if source of supply or disconnect is out of sight. Also, if source of supply is out of sight, XFMR required to be labelled as to source of supply.
10/27/2014TransferEF1Correct Below Sales floor large ceiling fansCannot have hardwired SO cord.
10/27/2014TransferEF1Correct Below Sales floor large ceiling fans.Disconnects within the fan blade radius or located so that fan blades violate working clearances.
10/27/2014TransferEF1Correct Below Entry heaters Tork digital time switches.Cannot use green wire as hot jumper.
10/27/2014TransferEF1Correct Below Sales floor.Several large ceiling paddle fans not shown on dwgs. Who did this work?
10/27/2014TransferEF1Correct Below Freezer condensate heat trace.Needs GFPE.
10/27/2014TransferEF1Correct Below Rooftop AC3WR recept. In use cover.
10/27/2014TransferEF1Correct Below Entry pnl feeding htrs, air curtains.Make breaker designations specific.
10/27/2014TransferEF1Correct Below Change orderComplete, show new pnl feeding entry ckts