| Date | Status | Code | Description | Ref | Location | Comments |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Entry heaters Tork digital time switches. | Cannot use green wire as hot jumper. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Change order | Complete, show new pnl feeding entry ckts |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Entry pnl feeding htrs, air curtains. | Make breaker designations specific. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Rooftop AC3 | WR recept. In use cover. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | General | May be more. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Change order dwgs. | Confirm that OCPD size, panel conforms to dwgs. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Sales floor large fans. | Controller is listed as an industrial control panel. No overall listing for the fan. Provide any manufacturers info / instructions to electrical plan reviewer at abuobaiddh@muni.org |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Sales floor large fans | Flex feeding fan fused disconnect not properly supported. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Sales floor large fans. | Cord neutral used as hot needs to be reidentified. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Sales floor large ceiling fans. | Disconnects within the fan blade radius or located so that fan blades violate working clearances. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Sales floor large ceiling fans | Cannot have hardwired SO cord. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Comtrollers for air curtains: entry. | Will need ladder to inspect. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | 277V-120V control transformer. | Ground one leg. Use ground bar. |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Sales floor. | Several large ceiling paddle fans not shown on dwgs. Who did this work? |
| 10/8/2014 | Transfer | EF1 | Correct Below | | Freezer condensate heat trace. | Needs GFPE. |