Inspection #: 324081
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Cancel
Comment: AM Requested by: Brandon 887-9132

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/8/2014TransferEF1Correct Below Entry heaters Tork digital time switches.Cannot use green wire as hot jumper.
10/8/2014TransferEF1Correct Below Change orderComplete, show new pnl feeding entry ckts
10/8/2014TransferEF1Correct Below Entry pnl feeding htrs, air curtains.Make breaker designations specific.
10/8/2014TransferEF1Correct Below Rooftop AC3WR recept. In use cover.
10/8/2014TransferEF1Correct Below GeneralMay be more.
10/8/2014TransferEF1Correct Below Change order dwgs.Confirm that OCPD size, panel conforms to dwgs.
10/8/2014TransferEF1Correct Below Sales floor large fans.Controller is listed as an industrial control panel. No overall listing for the fan. Provide any manufacturers info / instructions to electrical plan reviewer at abuobaiddh@muni.org
10/8/2014TransferEF1Correct Below Sales floor large fansFlex feeding fan fused disconnect not properly supported.
10/8/2014TransferEF1Correct Below Sales floor large fans.Cord neutral used as hot needs to be reidentified.
10/8/2014TransferEF1Correct Below Sales floor large ceiling fans.Disconnects within the fan blade radius or located so that fan blades violate working clearances.
10/8/2014TransferEF1Correct Below Sales floor large ceiling fansCannot have hardwired SO cord.
10/8/2014TransferEF1Correct Below Comtrollers for air curtains: entry.Will need ladder to inspect.
10/8/2014TransferEF1Correct Below 277V-120V control transformer.Ground one leg. Use ground bar.
10/8/2014TransferEF1Correct Below Sales floor.Several large ceiling paddle fans not shown on dwgs. Who did this work?
10/8/2014TransferEF1Correct Below Freezer condensate heat trace.Needs GFPE.