Inspection #: 309799
Inspection Type: Final Electrical
Inspector:
Result:
Comment: Pls call Brandon prior to going to jobsite 887-9132 Requested by: brandon marshall 887-9132 brandon@marshallselectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/9/2014 EF1Correct Below Administrative.Speak to chief of building inspections about underground covered without inspection.
7/9/2014 EF1Correct Below Dist pnl H10.Breaker feeding pnl H9 is shown on dwgs as 100A, not 70A as installed.
7/9/2014 EF1Correct Below   
7/9/2014 EF1Correct Below Canopy electrical work: airdoors and CRVsShown on dwgs: Who did this work? Not Marshall's Electric.
12/2/2013 EF1Correct Below Light switchesNeed barrier between ckts with 480V between.
12/2/2013 EF1Correct Below Approved dwgsDo not show or include in load calc, (12) HBH circuits.
12/2/2013 EF1Correct Below High emergency light in center.Not coming on.