Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 308097
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Please call before going to jobsite Requested by: brandon marshall 887-9132 brandon@marshallselectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/9/2014TransferEF1Correct Below 277V-120V control transformer.Ground one leg. Use ground bar.
7/9/2014TransferEF1Correct Below Dist pnl H10.Breaker feeding pnl H9 is shown on dwgs as 100A, not 70A as installed.
7/9/2014TransferEF1Correct Below   
7/9/2014TransferEF1Correct Below Freezer condensate heat trace.Needs GFPE.
7/9/2014TransferEF1Correct Below Sales floor.Several large ceiling paddle fans not shown on dwgs. Who did this work?
7/9/2014TransferEF1Correct Below Canopy electrical work: airdoors and CRVsShown on dwgs: Who did this work? Not Marshall's Electric.
7/9/2014TransferEF1Correct Below Change orderComplete, show new pnl feeding entry ckts
7/9/2014TransferEF1Correct Below Entry pnl feeding htrs, air curtains.Make breaker designations specific.
7/9/2014TransferEF1Correct Below Rooftop AC3WR recept. In use cover.
7/9/2014TransferEF1Correct Below Administrative.Speak to chief of building inspections about underground covered without inspection.
12/2/2013TransferEF1Correct Below Approved dwgsDo not show or include in load calc, (12) HBH circuits.
12/2/2013TransferEF1Correct Below Light switchesNeed barrier between ckts with 480V between.
12/2/2013TransferEF1Correct Below High emergency light in center.Not coming on.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS