Inspection #: 276181
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: CONTACT TIM, 503-502-8899 *DAVID ABUOBAID WOULD LIKE TO BE INFORMED OF THE TIME OF THE INSPECTION SO THAT HE CAN BE PRESENT

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/2/2013TransferEF1Correct Below Dist pnl H10.Breaker feeding pnl H9 is shown on dwgs as 100A, not 70A as installed.
12/2/2013TransferEF1Correct Below Approved dwgsDo not show or include in load calc, (12) HBH circuits.
12/2/2013TransferEF1Correct Below Light switchesNeed barrier between ckts with 480V between.
12/2/2013TransferEF1Correct Below High emergency light in center.Not coming on.
12/2/2013TransferEF1Correct Below 277V-120V control transformer.Ground one leg (white)
12/2/2013TransferEF1Correct Below Administrative.Speak to chief of building inspections about underground covered without inspection.
12/2/2013TransferEF1Correct Below Canopy electrical work: airdoors and CRVsShown on dwgs: Who did this work? Not Marshall's Electric.
12/2/2013TransferEF1Correct Below Sales floor.Several large ceiling paddle fans not shown on dwgs. Who did this work?
12/2/2013TransferEF1Correct Below Freezer condensate heat trace.Needs GFPE.
12/2/2013TransferEF1Correct Below   