Inspection #: 275950
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Requested by: BRANDON MARSHALL 907-887-9132 BRANDON@MARSHALLSELECTRIC.COM

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/22/2013TransferEF1Correct Below   
11/22/2013TransferEF1Correct Below Light switchesNeed barrier between ckts with 480V between.
11/22/2013TransferEF1Correct Below Dist pnl H10.Breaker feeding pnl H9 is shown on dwgs as 100A, not 70A as installed.
11/22/2013TransferEF1Correct Below Approved dwgsDo not show or include in load calc, (12) HBH circuits.
11/22/2013TransferEF1Correct Below High emergency light in center.Not coming on.
11/22/2013TransferEF1Correct Below 277V-120V control transformer.Ground one leg (white)
11/22/2013TransferEF1Correct Below Administrative.Speak to chief of building inspections about underground covered without inspection.