| Date | Status | Code | Description | Ref | Location | Comments |
| 11/22/2013 | Transfer | EF1 | Correct Below | | | |
| 11/22/2013 | Transfer | EF1 | Correct Below | | Light switches | Need barrier between ckts with 480V between. |
| 11/22/2013 | Transfer | EF1 | Correct Below | | Dist pnl H10. | Breaker feeding pnl H9 is shown on dwgs as 100A, not 70A as installed. |
| 11/22/2013 | Transfer | EF1 | Correct Below | | Approved dwgs | Do not show or include in load calc, (12) HBH circuits. |
| 11/22/2013 | Transfer | EF1 | Correct Below | | High emergency light in center. | Not coming on. |
| 11/22/2013 | Transfer | EF1 | Correct Below | | 277V-120V control transformer. | Ground one leg (white) |
| 11/22/2013 | Transfer | EF1 | Correct Below | | Administrative. | Speak to chief of building inspections about underground covered without inspection. |