Inspection #: 269762
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Cancel
Comment: Pls call Brandon 20 minutes prior to gong to jobsite 887-9132 Requested by: brandon marshall 887-9132 brandon@marshallselectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/25/2014TransferEF1Correct Below Comtrollers for air curtains: entry.Will need ladder to inspect.
9/25/2014TransferEF1Correct Below Entry pnl feeding htrs, air curtains.Make breaker designations specific.
9/25/2014TransferEF1Correct Below Rooftop AC3WR recept. In use cover.
9/25/2014TransferEF1Correct Below Freezer condensate heat trace.Needs GFPE.
9/25/2014TransferEF1Correct Below GeneralMay be more.
9/25/2014TransferEF1Correct Below Entry heaters Tork digital time switches.Cannot use green wire as hot jumper.
9/25/2014TransferEF1Correct Below Change orderComplete, show new pnl feeding entry ckts
9/25/2014TransferEF1Correct Below Change order dwgs.Confirm that OCPD size, panel conforms to dwgs.
9/25/2014TransferEF1Correct Below Sales floor large fans.Controller is listed as an industrial control panel. No overall listing for the fan. Provide any manufacturers info / instructions to electrical plan reviewer at abuobaiddh@muni.org
9/25/2014TransferEF1Correct Below Sales floor large fansFlex feeding fan fused disconnect not properly supported.
9/25/2014TransferEF1Correct Below Sales floor large fans.Cord neutral used as hot needs to be reidentified.
9/25/2014TransferEF1Correct Below Sales floor large ceiling fans.Disconnects within the fan blade radius or located so that fan blades violate working clearances.
9/25/2014TransferEF1Correct Below Sales floor large ceiling fansCannot have hardwired SO cord.
9/25/2014TransferEF1Correct Below 277V-120V control transformer.Ground one leg. Use ground bar.
9/25/2014TransferEF1Correct Below Sales floor.Several large ceiling paddle fans not shown on dwgs. Who did this work?