| 4/11/2013 | Transfer | EF1 | Correct Below | | | progress rough for coolers and freezers and prelim look at service. |
| 4/11/2013 | Transfer | EF1 | Correct Below | | Is cooler / freezer control power class 2? | |
| 4/11/2013 | Transfer | EF1 | Correct Below | | Walk in cooler air door. | Possible issues with working clearance. |
| 4/11/2013 | Transfer | EF1 | Correct Below | | Service. | Line side bonding 3/0 is too small for (6) service latteral conduits. |
| 4/11/2013 | Transfer | EF1 | Correct Below | | | |
| 4/11/2013 | Transfer | EF1 | Correct Below | | Comment | Progress inspection. |
| 4/11/2013 | Transfer | EF1 | Correct Below | | Rooftop condensor J. | X-bracing in front of control panel violates 110.26 working clearances. |
| 4/11/2013 | Transfer | EF1 | Correct Below | | Mechanical mezzanine | Refrigeration compressor rack has (2) listed industrial control panels. No apparent listing for rack as a whole. |