Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 235509
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: rough & Final on Bakery cooler/ freezer, Produce cooler Requested by: Ray 206-407-7960

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/3/2013TransferEF1Correct Below Walk in cooler air door.Possible issues with working clearance.
4/3/2013TransferEF1Correct Below Service.Line side bonding 3/0 is too small for (6) service latteral conduits.
4/3/2013TransferEF1Correct Below   
4/3/2013TransferEF1Correct Below  progress rough for coolers and freezers and prelim look at service.
4/3/2013TransferEF1Correct Below Is cooler / freezer control power class 2? 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter