Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
06 5416
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
3101 PENLAND PKWY Anchorage
Location:
Work Description:
Work Descr: T/I, Remarks: jrd
Status:
Closed
Project Name:
GNC LIVE WELL
Review Type:
Electrical
Result:
Approved
Result Date:
8/11/2006 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): 8-11-06. THE ENGINEER CALLED ME FROM SEATTLE AND INFORMED ME THAT THERE ARE NO LOAD ADDED TO THE PLAN, ONLY CHANGE LIGHT FITURE ONE FOR ONE. APPROVED The following comments are based on the 2005 National Electrical Code and should be resolved before a permit is issued. This correction list is not a building permit. The approval of plans and specifications does not permit the violation of any section of the NEC, or any federal, state or local amendments to these codes. C(2): ARC-FLASH MARKING: Sheet E-2 (Panel Schedule - Arc Flash Protection Marking). Article 110-16 requires that switchboards, panel boards, industrial control panels, and motor control centers that are likely to required examination, adjustment, servicing, or maintenance while energized shall be field marked to warn qualified persons of potential electric Arc Flash Hazards.The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing or maintenance. Please add marking to the plan.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501