Permit Number: E05 5931
Permit Type: Commercial Trade Permit - Addition Electrical
Address: 7010 SAND LAKE RD Anchorage
Location:
Work Description: Work Descr: install an exterior walk-in freezer on a concrete pad. freeser dimensions are 24'x8'x8', slab dimensions underneath are 25'x9' // 192 sq ft freezer, $1,500 concrete slab, Remarks: mgm
Status: Closed
Project Name: FISH & WILDLIFE WAREHOUSE
Review Type: Structural
Result: Approved
Result Date: 9/8/2005 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

C(1): The ICC report does not reference seismic lateral loads and the L12 connection as detailed appears to be poorly suited to resist cyclic shear loads associated with sliding. The anchor as detailed appears to be suitable for overturning loads. With the unit elevated by the skids, loads will be placed on the anchor above the base of the anchor. The recommended edge distance for the 3/4" HY-150 anchoris greater than that specified by the manufacturer for the L12 anchor. An independent shear connection is recommended in each direction away from the slab corners.