Permit Number: 05 5858
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1717 TIDEWATER RD Anchorage
Location:
Work Description: Work Descr: change of use - converting warehouse into office area, Remarks: cs - call sean for contact info - see contacts page
Status: Closed
Project Name: PORT OF ANCHORAGE
Review Type: Architectural
Result: Approved
Result Date: 9/7/2005 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments based on the 2000 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. C(2): A1.1, A2.1: Reference the new exterior exit stair. Stairways must have a solid surface per section 1003.3.3.5.1. In this case, grip strut is specified. Per the exception, grip strut may be used on S occupancies, but in this case the stair serves a B occupancy. Please address. Also note that exterior stairs must be protected from the accumulation of ice and snow per section 1003.3.3.5.2. Grip strut can meet this requirement, but cannot be used to serve a B occupancy. Resolved 9-7-05 per alternate methods approval to use grip strut based on use of facility.