Permit Number: 05 5319
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: Work Descr: R&R UPPER ROOF ASSEMBLY OF THE INSTRUCTIONAL MEDIA CENTER, Remarks: PJB // items remaining on CCO: provide change order for insulation of handrail maintain barricades in place until installation -mgm
Status: Closed
Project Name: WEST HIGH IMC ROOF UPGRADES
Review Type: Structural
Result: Approved
Result Date: 6/9/2005 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): No structural calculations have been provided. Please provide structural calculations as requested by the following comments. C(2): For the reroofing of the high roof area, calculations of the structural supporting members of the existing must be provided unless the new system does not add more than 5% weight to the structure. Please tabulate the weights of existing roofing material and the new existing materials to show that the weight of the new roofing system doesnot change the design basis of the existing members. 5/9/05 The response provided shows that the new roof system will be lighter than the existing and gravity and lateral load effects will not require additional evaluation per the Anchorage Existing Building Code.