Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
05 5215
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
3101 PENLAND PKWY Anchorage
Location:
Work Description:
Work Descr: T/I, Remarks: jrd
Status:
Closed
Project Name:
JOANN SUPERSTORE
Review Type:
Fire
Result:
Approved
Result Date:
5/14/2005 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
C(1): FIRE REVIEW STATUS: DISAPPROVED 4/6/05 Carpenter See Permit 05 -5232.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501