Permit Number: 05 5039
Permit Type: Commercial Building Permit - None BldgAdd
Address: 6201 BOEING AVE Anchorage
Location:
Work Description: Work Descr: 12,600 sq ft warehouse expansion of BLDG B @ alaska carport, Remarks: tb **CCO conditions - electrical per V. Fosberg report, structural - completion of change order #3**
Status: Closed
Project Name: NORTHWEST AIRLINES CARGO PORT
Review Type: Fire
Result: Approved
Result Date: 5/9/2005 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): FIRE FLOW: Required fire flow is 1500 GPM for a sprinklered building. AWWU projection shows 1228 GPM available. An actual flow test may be required to prove required flow. Please address. C(2): EMERGENCY LIGHTING: Provide at exterior exit discharges per IBC 1003.2.11.