Permit Number:
04 5366
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
2500 MINNESOTA DR Anchorage
Location:
Work Description:
Work Descr: renovation af all bathrooms and replacement of security, Remarks: cs
Status:
Closed
Project Name:
ROMIG MIDDLE SCHOOL
Review Type:
Architectural
Result:
Approved
Result Date:
5/27/2004 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): The following comments are based on the 2000 International Building Code (IBC) and ANSI A117.1 and must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. C(2): Please see details 1, 2, and 3 on sheet A2.1. Per ANSI A117.1, section 404.2.4.1 and table 404.2.4.1 maneuvering clearance at swing doors with forward approach from the latch side are required to have a minimum 18" beyond the latch parallel to the door. If you revise the door swing in, all requirements are met.