Permit Number: 04 5349
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1980 ANCHORAGE PORT RD Anchorage
Location:
Work Description: Work Descr: 2704 sqft. type IIIB mezz/ and alteration, Remarks: gjs CO #1 NEEDS APPROVED BEFORE CO IS ISSUED
Status: Closed
Project Name: USCG TEMP MSST
Review Type: Structural
Result: NA
Result Date: 1/27/2010 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): This review is based on the requirements of the 2000 International Building Code (IBC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations. C(2): CONNECTION OF STAIRS TO BUILDING The calcs indicate that the stairs will be attached to the building at the top to resist lateral forces but no connection is indicated on the plans for the south or north stair. Please detail this connection. Reference: IBC section 1603.1.