Permit Number: 04 5349
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1980 ANCHORAGE PORT RD Anchorage
Location:
Work Description: Work Descr: 2704 sqft. type IIIB mezz/ and alteration, Remarks: gjs CO #1 NEEDS APPROVED BEFORE CO IS ISSUED
Status: Closed
Project Name: USCG TEMP MSST
Review Type: Plumbing
Result: Approved
Result Date: 6/29/2004 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments based on the 2000 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform plumbing Code or any federal, state or local regulations. SATISFIED PER RESUBMITTAL COMMENTS RECEIVED 5-26-04. C(2): 1/M5.1: The 3 inch horizontal waste line serving 4 water closets must be upsized in accordance with Table 7-5. The 2 inch waste line serving one water closet must also be upsized accordingly. APPROVED UPON RECEIPT AND APPROVAL OF RESUBMITTED DRAWINGS BASED UPON RESUBMITTAL COMMENTS RECEIVED 5-26-04. RECEIVED DRAWINGS 6-22-04.