Permit Number: 04 5349
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1980 ANCHORAGE PORT RD Anchorage
Location:
Work Description: Work Descr: 2704 sqft. type IIIB mezz/ and alteration, Remarks: gjs CO #1 NEEDS APPROVED BEFORE CO IS ISSUED
Status: Closed
Project Name: USCG TEMP MSST
Review Type: Electrical
Result: Approved
Result Date: 6/29/2004 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments are based on the 2002 National Electrical Code and should be resolved before a permit is issued. This correction list is not a building permit.The approval of plans and specifications does not permit the violation of any section of the NEC, or any federal, state or local amendments to these codes. 6-29-04. NO RESPONSE IS REQUIRED. C(2): Sheet E 4.1 (One Line Diagram - Arc Flash Protection Marking). Article 110-16 requires that switchboards, panel boards, industrial control panels, and motor control centers that are likely to required examination, adjustment, servicing, or maintenance while energized shall be field marked to warn qualified persons of potential electric Arc Flash Hazards. The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing or maintenance INSPECTOR TO VERIFY THE ARC FLASH MARKING ON EVERY PANEL.