Permit Number: 04 5275
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2841 DEBARR RD Anchorage
Location:
Work Description: Work Descr: Tenant improvement **MCC Paid Back Flow Preventor testing fee09-13-2005 / pjb***, Remarks: gjs
Status: Closed
Project Name: ANCHORAGE RADIATION THERAPY CE
Review Type: Mechanical
Result: Approved
Result Date: 6/16/2004 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments based on the 2000 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. APPROVED PER RESUBMITTAL RECEIVED 6-4-04. C(2): Ref. mechanical drawing M3.1: Room #'s 107, 125, 126 and 129 appear to be missing a return air grille. Please clarify the return air path. APPROVED PER RESUBMITTAL RECEIVED 6-4-04.