Permit Number:
04 5275
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
2841 DEBARR RD Anchorage
Location:
Work Description:
Work Descr: Tenant improvement **MCC Paid Back Flow Preventor testing fee09-13-2005 / pjb***, Remarks: gjs
Status:
Closed
Project Name:
ANCHORAGE RADIATION THERAPY CE
Review Type:
Fire
Result:
Approved
Result Date:
7/15/2004 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): FIRE PROTECTION SYSTEMS: A separate submittal review and permit is required for additions and/or changes to the fire alarm & sprinkler system. C(2): EMERGENCY LIGHTING: Provide as required per IBC 1003.2.11. Lighting level of 1 ft candle is required at floor level along the path of egress to include the exit discharge. Add additional lighting where required and show all fixtures to include existing. The 3 fixtures as shown do not appear adequate.