Permit Number: 04 5214
Permit Type: Commercial Building Permit - None BldgNew
Address: 9138 ARLON ST Anchorage
Location:
Work Description: Work Descr: 7319 sqft -occup M/ 8545 sqft- occup B, Remarks: gjs
Status: Closed
Project Name: LIBERTY VILLAGE
Review Type: Architectural
Result: Approved
Result Date: 5/27/2004 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments are based on the 2000 International Building Code (IBC) and must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. C(2): NON-SEPARATED USES It appears that you are using IBC section 302.3.2 (non-separated uses) to determine your allowable height and area. Type V-B occupancy M buildings are only allowed to be 1 story, but you are allowed a 1 story increase for a fully sprinklered building. Please update the code study to reflect this. Reference: IBC section 504.2. 4/30/04 - Non separated uses applied to both area and height of the building. Please update the code study.