Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: 04 5145
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: Tenant Improvement, Remarks: tb
Status: Closed
Project Name: QUIZNOS SUB
Review Type: Structural
Result: Approved
Result Date: 6/10/2004 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): This review is based on the requirements of the 2000 International Building Code and all adopted references thereto as amended by MOA. The following comments must be addressed before permit can be issued. C(2): Reference IBC Section 1621: Architectural, mechanical and electrical components must be attached and anchorage to the building in accordance with this section. Mechanical and electrical components, weighing 20 lbs or less, where Ip = 1.0, and flexible connections between the components and associated duct work, piping and conduit are provided are exempt from these requirements. VAV boxes, and soffits may require design and detailing. Please verify and provide the required engineering calculations and add details and/or notes on the plans for construction.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS