Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: Tenant Improvement, Remarks: tb
Status: Closed
Project Name: QUIZNOS SUB
Review Type: Fire
Result: Approved
Result Date: 3/31/2004 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): FIRE PROTECTION SYSTEMS: Provide separate submittal, review, permit & approval for sprinkler, fire alarm and hood suppression system. Hood system shall be connected to terminal fire alarm system. A manual reset shall be provided to electrically operated gas valves supplying the hood system. Add horn/strobes in the work area as requiredto meet code. C(2): FIRE EXTINGUISHER: Provide as required per IFC 906 for size, distribution, location and type. A multipurpose extinguisher is required within 75 ft travel distance to the work area. A "K Class" is required within 30 ft of the hood system. Both will be field verified at final inspection.