Permit Number: 03 6084
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3901 OLD SEWARD HWY Anchorage
Location:
Work Description: Work Descr: Tenant improvement, Remarks: gjs
Status: Closed
Project Name: SADLERS HOME FURNISHING
Review Type: Structural
Result: Approved
Result Date: 12/5/2003 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Reference Structural Plans: Please provide Construction Documents (structural plans) for Building Safety reviewand approval, and assure that all plans are stamped and signed by engineer of record. 1603.1 and Building Code Local Amendments I-23.10.302.2 12-16-03 JCRC: Please consider that combining structural plans in to the architectural plans is not conventional, but it has been approved with the condition that the engineer of record stamps and signs the applicable plans as well. C(2): Reference new Framing of store front and Log structure: Please provide on the plans the framing and details of the new store front and log structure, referenced on sheets D1.1 and A5.1, along with supporting calculations. Please show in your calculations the expected loads on the existing elements and the design capacity of the new elements to develop the loads. 1604.4 12-16-03 JCRC: Please clearly identify on the plans the locations where the steel columns, per detail 4/S6.4, are intended and provide details showing the anchoring of the log walls to the existing slab on grade.